Single Phase to 3 Phase Converter
The SDT series single-phase to three-phase converter, adopted AC-DC-AC circuit structure and using SPWM modulation control technology, which can convert ordinary single-phase power to industrial three-phase power. After through SDT series single-phase to three-phase converter power conversion, the three-phase power output is standard pure sine wave, the harmonic distortion rate(THD) is less than 2%, totally meet the national standards of three-phase power quality, applicable to all types of load.
The SDT series single-phase to three-phase converter can solve production inconvenience because of some areas with the three-phase electric power restrictions, also solved some user requirements that can apply for the three-phase electric because of space limitation.
Technical Features:
Technical Data
Model | SDT-8KW | |
Isolation | Low Frequency Transformer | |
AC Input | Input rated voltage(VAC) | Single phase 110V |
Input voltage range | 110/120/220/230/240Vac optional | |
Input rated current(A) | 72.7A | |
AC Output | Rated AC output power | 8KW |
AC output waveform | Pure sine wave | |
Phases | Three phase, 4 wires | |
Output rated voltage | 220VAC , ,3% | |
Output voltage range | 220/230/240/380/400/415/440/480Vac optional | |
Output Frequency | 50Hz/60Hz , ,0.05Hz | |
Output rated current(A) | 20.9A (per phase) | |
Power Factor(PF) | 0.9 | |
Overload Ability | 150%, 10s | |
Efficiency | >93% | |
Waveform distortion rate (THD) | <3%(Linear load) | |
Crest Factor (CF) | 3:1 | |
Display | LCD | |
Electrical insulation properties | 2500Vac, 1 Minute | |
Ambient temperature | -15 ,55 | |
Using environment humidity | 0,90%,No condensation | |
Protection | Input under voltage, overvoltage, output over-current, short circuit, overheating etc. | |
Structure | Cooling method | Fan-cooled |
Noise | <40dB | |
Degree of protection | IP20(indoor) | |
Using altitude(m) | 3000 | |
Dimensions (mm) | 630 x 630 x 900mm | |
Weight (Kg) | 100Kg | |
CE Standard | EN60950-1:2006+A11:2009, EN61000-6-4:2007+A1:2001, EN61000-6-2:2005, EN61000-3-12:2005, EN61000-3-11:2000 |